Section 5.5.8
Nuts and Bolts of Jolts:
Lightning Safety in the Mining Industry
By Richard Kithil, President & CEO, NLSI
1. Abstract
Investigations at various mine locations worldwide disclose many power quality and safety issues traceable to ignoring lightning safety. Some examples are:
- Mine-wide mobile radio communications fail following a lightning strike to a central radio tower. Surge protection was not adequate. (Canada)
- Five maintenance workers are injured when lightning strikes a stationary vehicle. The lightning early warning system is low cost and old technology. (Peru)
- A central computer system is damaged by a lightning strike. Important geological data is lost. Grounding methods are in violation of codes and standards. (U.S.)
- More than $US one million is spent on some 350 unconventional-design lightning rods. The product is not approved by U.S. or international lightning protection codes and standards. Safety to all buildings is compromised. (Peru)
- A mine has no policies/procedures in effect for lightning safety. Accidents under dangerous conditions result in production delays and liabilities for management. (Australia)
- Miners are killed when lightning exploded methane gas inside a subsurface mine. A comprehensive approach to lightning safety is absent. (U.S. and Russia and China)
- Four of eight gas turbine generators suffer lightning-induced failures. Production losses at the mine are $700,000/day. The power shortage lasts three months. (Papua New Guinea)
- Lightning causes failure of a primary water pumping system. Underground flooding closes the mine for 45 days. (South Africa)
- Smelter potline is “frozen” after lightning hits a substation. 164 pots have to be dug out by hand. Production is shut down for seven weeks. (U.S.)
- Haul truck is struck by lightning with consequential tire explosion. Grenade-like fragments kill two workers. (Mexico)
- Mine superintendent standing outside during a thunderstorm is killed by lightning. (Australia)
- Radio operator inside a building is killed by lightning. Grounding is poor. (Indonesia)
With such examples, it is difficult to support a position that lightning incidents are rare. This paper suggests that lightning is responsible for significant economic and personal costs in the industry. How to defend against the lightning hazard at mining operations? We recommend adoption of a lightning hazard mitigation and safety planning process that can be applied to most facilities.
2. Lightning Behavior and Characteristics
2.1. Physics of Lightning
Lightning’s characteristics include current levels approaching 250 kA with the 50% average being about 25kA, temperatures to 15,000 C, and voltages in the hundreds of millions. There are some ten cloud-to-cloud lightnings for each cloud-to-ground lightning flash. Globally, some 2,000 on-going thunderstorms generate about 50-100 lightning strikes to earth per second. Lightning is the agency that maintains the earth’s electrical balance. The phenomenology of lightning flashes to earth, as presently understood, follows an approximate behavior: the downward leader (gas plasma channel) from a thundercloud pulses toward earth. Ground-based air terminators, such as fences, trees, blades of grass, corners of buildings, people, lightning rods, and power poles, emit varying degrees of induced electric activity. They may respond at breakdown voltage by forming upward streamers. In this intensified local field, some leader(s) likely will connect with some streamer(s). Then, the "switch" is closed and the current flows. Lightning flashes to ground are the result. A series of return strokes follow.
2.2 Lightning Effects
Thermal stress of materials around the attachment point is determined by:
- heat conduction from arc root
- heat radiation from arc channel
- Joule heating
The radial acoustic shock wave (thunder) can cause mechanical damage. Magnetic pressures — up to 6,000 atmospheres for a 200 kA flash — are proportional to the square of the current and inversely proportional to the square of the diameter of struck objects. Voltage sparking is a result of dielectric breakdown. Thermal sparking is caused is caused when melted materials are thrown out from hot spots. Exploding high current arcs, due to the rapid heating of air in enclosed spaces, have been observed to fracture massive objects (such as concrete and rocks). Voltage transfers from an intended lightning conductor into electrical circuits can occur due to capacitive coupling, inductive coupling, and/or resistance (i.e., insulation breakdown) coupling. Transfer impedance, due to loss of skin effect attenuation or shielding, can radiate interference and noise into power and signal lines. Transfer inductance (mutual coupling) can induce voltages into a loop that can cause current flows in other coupled circuits.
2.3 Behavior of Lightning
Absolute protection from lightning may exist in a thick-walled and fully enclosed Faraday Cage; however, this is impractical in most cases. Lightning “prevention” exists only as a vendor-inspired marketing tool. Important new information about lightning may affect sensitive facilities. First, the average distance between successive cloud-to-ground flashes is greater than previously thought. The old recommended safe distance from the previous flash was 1-3 miles. New information suggests that a safe distance should be 6-8 miles (Lopez and Holle, National Severe Storm Center, 1998). Second, some 40% of cloud-to-ground lightnings are forked, with two or more attachment points to the earth. This means there is more lightning to earth than previously measured (Krider, Intl. Conf. Atmospheric Electricity,1998). Third, radial horizontal arcing in excess of 20 m from the base of the lightning flash extends the hazardous environment (Sandia Labs, 1997). Lightning is a capricious, random, stochastic, and unpredictable event. At the macro-level, much about lightning is understood. At the micro-level, much has yet to be learned.
When lightning strikes an asset, facility, or structure (AFS), return-stroke current will divide up among all parallel conductive paths between attachment point and earth. Division of current will be inversely proportional to the AFS path impedance, Z (Z = R + XL, resistance plus inductive reactance). The resistance term will be low, assuming effectively bonded metallic conductors. The inductance, and related inductive reactance, presented to the total return stroke current will be determined by the combination of all the individual inductive paths in parallel. Essentially lightning is a current source. A given stroke will contain a given amount of charge (coulombs = amp/seconds) that must be neutralized during the discharge process. If the return stroke current is 50kA — that is the magnitude of the current that will flow, whether it flows through one ohm or 1,000 ohms. Therefore, achieving the lowest possible impedance serves to minimize the transient voltage developed across the AFS path through which the current is flowing [e(t) = I (t)R + L di/dt)].
3. Lightning Protection Designs
Mitigation of lightning consequences can be achieved by the use of a detailed systems approach, described below in general terms.
3.1 Air Terminals
Since Franklin's day, lightning rods have been installed upon ordinary structures as sacrificial attachment points, intending to conduct direct flashes to earth. This integral air terminal design does not provide protection for electronics, explosives, or people inside modern structures. Inductive and capacitive coupling (transfer impedance) from lightning-energized conductors can result in significant voltages and currents on interior power, signal and other conductors. Overhead shield wires and mast systems located above or next to the structure are suggested alternatives in many circumstances. These are termed indirect air terminal designs. Such methods presume to collect lightning above or away from the sensitive structure, thus avoiding or reducing flashover attachment of unwanted currents and voltages to the facility and equipments. These designs have been in use by the electric power industry for over 100 years. Investigation into applicability of dielectric shielding may provide additional protection where upward leader suppression may influence breakdown voltages (Sandia Laboratories, 1997). Faraday-like interior shielding, either via rebar or inner-wall screening, is under investigation for critical applications (U.S. Army Tacom-Ardec).
Unconventional air terminal designs that claim the elimination or redirecting of lightning (DAS/CTS - charge dissipators) or lightning preferential capture (early streamer emitters - ESE) deserve a very skeptical reception. Their uselessness has been well-described in publications such as NASA/Navy Tall Tower Study, 1975; R.H. Golde, “Lightning,” 1977; FAA Airport Study, 1989; T. Horvath, “Computation of Lightning Protection,” 1991; D. MacKerras et al., IEE Proc-Sci Meas. Technol, V. 144, No. 1 1997; National Lightning Safety Institute, “Royal Thai Air Force Study,” 1997; A. Mousa, “IEEE Trans. Power Delivery, V. 13, No. 4 1998; International Conference on Lightning Protection - Technical Committee personal correspondence, 2000; Uman and Rakov, “Critical Review of Nonconventional Approaches to Lightning Protection,” AMS Dec. 2002.
Radioactive air terminals have been banned in Europe following investigations by reputable scientists (R.H. Golde, op. cit. and C.B. Moore, personal correspondence, 2000).
3.2 Downconductors
Downconductor pathways should be installed outside of the structure. Rigid strap is preferred to flexible cable due to inductance advantages. Conductors should not be painted, since this will increase impedance. Gradual bends always should be employed to avoid flashover problems. Building structural steel also may be used in place of downconductors where practical as a beneficial subsystem emulating the Faraday Cage concept.
3.3 Bonding
Bonding assures that unrelated conductive objects are at the same electrical potential. Without proper bonding, lightning protection systems will not work. All metallic conductors entering structures (e.g., AC power lines, gas and water pipes, data and signal lines, HVAC ducting, conduits and piping, railroad tracks, overhead bridge cranes, roll up doors, personnel metal door frames, hand railings) should be electrically referenced to the same ground potential. Connector bonding should be exothermal and not mechanical wherever possible, especially in below-grade locations. Mechanical bonds are subject to corrosion and physical damage. HVAC vents that penetrate one structure from another should not be ignored as they may become troublesome electrical pathways. Frequent inspection and cross-joint measuring (maximum 10 milliohms) of connectors to assure continuity is recommended.
3.4 Grounding
The grounding system must address low earth impedance as well as low resistance. A spectral study of lightning's typical impulse reveals both a high- and a low-frequency content. The grounding system appears to the lightning impulse as a transmission line where wave propagation theory applies. A considerable part of lightning’s current responds horizontally when striking the ground: it is estimated that less than 15% of it penetrates the earth. As a result, low resistance values (25 ohms per NEC) are less important that volumetric efficiencies.
Equipotential grounding is achieved when all equipments within the structure(s) are referenced to a master bus bar, which in turn is bonded to the external grounding system. Earth loops and consequential differential rise times must be avoided. The grounding system should be designed to reduce AC impedance and DC resistance. The use of buried linear or radial techniques can lower impedance as they allow lightning energy to diverge as each buried conductor shares voltage gradients. Ground rings connected around structures are useful. Proper use of concrete footing and foundations (Ufer grounds) increases volume. Where high resistance soils or poor moisture content or absence of salts or freezing temperatures are present, treatment of soils with carbon, Coke Breeze, concrete, natural salts, or other low-resistance additives may be useful. These should be deployed on a case-by-case basis where lowering grounding impedances are difficult and/or expensive by traditional means.
3.5 Corrosion
Corrosion and cathodic reactance issues should be considered during the site analysis phase. Where incompatible materials are joined, suitable bi-metallic connectors should be adopted. Joining of aluminum down conductors together with copper ground wires is a typical situation promising future troubles.
3.6 Transients and Surges
Electronic and electrical protection approaches are well-described in IEEE1100. Ordinary fuses and circuit breakers are not capable of dealing with lightning-induced transients. Surge protection devices (SPD aka TVSS) may shunt current, block energy from traveling down the wire, filter certain frequencies, clamp voltage levels, or perform a combination of these tasks. Voltage clamping devices capable of handling extremely high amperages of the surge, as well as reducing the extremely fast rising edge (dv/dt and di/dt) of the transient are recommended.
It is suggested to protect the AC power main panel, all relevant secondary distribution panels, and all valuable plug-in devices, such as process control instrumentation, computers, printers, fire alarms, and data recording and SCADA equipment. Protecting incoming and outgoing data and signal lines (such as modems and LANs) is essential. All electrical devices that serve the primary asset, such as wellheads, remote security alarms, CCTV cameras, and high-mast lighting, should be included.
Transient limiters should be installed with short lead lengths to their respective panels. Under fast rise time conditions, cable inductance becomes important and high transient voltages can be developed across long leads. SPDs with replaceable internal modules are suggested.
In all instances, the use of high-quality, high-speed, self-diagnosing SPD components is suggested. Transient limiting devices may use spark gap, diverters, metal oxide varistors, gas tube arrestors, silicon avalanche diodes, or other technologies. Hybrid devices, using a combination of these techniques, are preferred. SPDs conforming to the European CE mark are tested to a 10 X 350 us waveform, while those tested to IEEE and UL standards only meet a 8 X 20 us waveform. It is suggested that user SPD requirements and specifications conform to the CE mark, as well as ISO 9000-9001 series quality control standards.
Uninterrupted power supplies (UPSs) provide battery backup in cases of power quality anomalies, such as brownouts, capacitor bank switching, outages, and lightning. UPSs are employed as back-up or temporary power supplies. They should not be used in place of dedicated SPD devices. Correct Category A installation configuration is: AC wall outlet to SPD to UPS to equipment.
3.7 Detection
The marketplace provides good/not good/poor products for lightning detection. They are available at differing costs and technologies and can be useful to provide early warning. Their sensors acquire lightning signals such as RF, EF, or light from cloud-to-cloud or cloud-to-ground or atmospheric gradients. Users should beware of over-confidence in detection equipment. It is not perfect and it does not always acquire all lightning all the time.
Detectors cannot “predict” lightning. Detectors cannot help with “bolt from the blue” events. An interesting application is their use to disconnect from AC line power and to engage standby power before the arrival of lightning. A notification system of radios, sirens, loudspeakers, or other communication means should be coupled with the detector. See An Overview of Lightning Detection Equipment for a more detailed treatment of detectors.
3.8 Testing and Maintenance
Modern diagnostic testing is available to “verify” the performance of lightning conducting devices as well as to indicate the general route of lightning through structures. With such techniques, lightning pathways can be inferred reliably. Sensors that register lightning current attachments can be fastened to downconductors. Regular physical inspections and testing should be a part of an established preventive maintenance program. Failure to maintain any lightning protection system may render it ineffective.
4. Personnel Safety Issues
Lightning safety should be practiced by all people during thunderstorms. Measuring lightning's distance is useful. Using the "flash/bang" (F/B) technique, for every five seconds — from the time of seeing the lightning flash to hearing the associated thunder — lightning is one mile away. For example, a F/B of 10 = 2 miles and a F/B of 20 = 4 miles. The distance from Strike A to Strike B to Strike C can be as much as 5-8 miles. The National Lightning Safety Institute recommends suspending all outdoor activities when lightning crosses a five-mile radius. These activities should not be resumed until 30 minutes has expired from the last observed thunder or lightning. This is a conservative approach: perhaps it is not practical in all circumstances.
If one is suddenly exposed to nearby lightning, adopting the so-called lightning safety position (LSP) is suggested. LSP means staying away from other people, removing metal objects, crouching with feet together, head bowed, and placing hands on ears to reduce acoustic shock from nearby thunder. When lightning threatens, standard safety measures should include: avoid water and all metal objects; get off the higher elevations including rooftops; avoid solitary trees; stay off the telephone. A fully enclosed metal vehicle —van, car, or truck — is a safe place because of the (partial) Faraday Cage effect. A large permanent building can be considered a safe place. Used shipping containers (MilVans/Conex) can be converted to safe shelters. In all situations, people should avoid becoming a part of the electrical circuit.
Every organization should consider adopting and promulgating a lightning safety plan specific to its operations. An all-encompassing general rule should be: “If you can hear it (thunder), clear it (evacuate); if you can see it (lightning), flee it.”
5. Codes and Standards
In the U.S. there is no single lightning safety code or standard providing comprehensive assistance. U.S. government lightning protection documents should be consulted. The Federal Aviation Administration FAA-STD-019d is valuable. The IEEE 142 and IEEE 1100 Recommended Practices are suggested. Other recommended federal codes include military documents MIL HDBK 419A, Army PAM 385-64, NAVSEA OP 5, AFI 32-1065, NASA STD E0012E, MIL STD 188-124B, MIL STD 1542B, MIL STD 5087B, and UFC 3-570-01.
The International Electrotechnical Commission IEC 62305 series for lightning protection is a comprehensive reference document for the lightning protection engineer. Adopted by many countries, IEC 62305 is a science-based document applicable to many design situations. Spanish-speaking mining operations should consult the Mexican lightning protection code NMX-J-549-ANCE. Beware the French NF C17-102 and the Spanish UNE-21186 codes, which are produced by enthusiastic salesmen, not by objective engineers and scientists.
6. Conclusion
Lightning has its own agenda and may cause damage despite application of best efforts. Any comprehensive approach for protection should be site-specific to attain maximum efficiencies. In order to mitigate the hazard, systematic attention to details of grounding, bonding, shielding, air terminals, surge protection devices, detection and notification, personnel education,
maintenance, and employment of risk management principles are recommended.
Areas of vulnerability at typical mines include: Security; Communications and Radio Towers; IT Operations; Gated Entrances; Conveyors and Crushers; Drilling; Loading; Hauling; Maintenance Buildings; Administrative Buildings; Laboratory Buildings; Cafeterias; Weigh Stations; Compressor and Pumping Stations; Guard Crossings; Exploration Crew Activities; Diesel Generator Stations and other locations specific to particular mine activities.
Protection now or protection later? Systematic risk management will assess the hazard and will employ defenses in advance of the threat.
7. References
International Conference on Lightning Protection (ICLP) Proceedings, Kanazawa (2006), Avignon (2004), Cracow (2002), Athens (2000), Birmingham (1998), and Florence (1996).
- IEEE STD 142-1991 Grounding of Industrial and Commercial Power Systems.
- IEEE STD 1100-1999 Powering and Grounding Electronic Equipment.
- IEEE Transactions on Electromagnetic Compatibility, Nov. 1998.
- National Research Council, Transportation Research Board, NCHRP Report 317, June 1989.
- International Electrotechnical Commission (IEC), International Standard for Lightning Protection. See: http://www.iec.ch.
- R.L. Gardner, Lightning Electromagnetics, Hemisphere Publishing, New York, NY, 1991.
- T. Williams and K. Armstrong, EMC for Systems and Installations, Newnes, Oxford, UK, 2000.
- R. Kithil, Lightning Protection for Engineers, NLSI, Louisville, CO, 2006.
|