 ~ National Lightning Safety Institute ~

Section 5.5.6

Lightning Protection for Telecommunications Facilities

By Richard Kithil, President & CEO, NLSI
Presented at the International Lightning Detection Conference, Tucson, AZ, April 2006

1. Summary

In 2004-2005, a major national insurance company was receiving lightning-related claims and paying compensation in the six figures to E911 Emergency Radio Operations customers across the U.S. Why were losses seemingly unrelated to lightning distribution, times of year, latitudes, elevations, ages of equipment, and the like? NLSI was engaged to visit sites in CO, TX, TN, AL, LA, GA, MI, and IL to investigate cause, effect, and remediation subjects. The purpose of this paper is to describe findings together with application of known mitigation defenses in general terms for application to telecommunications facilities.

2. Lightning Protection Sub-systems

A hierarchy of recognized application methods should be applied according to site realities. This matrix is depicted below:

  Direct Strike Indirect Strike Exterior Location Interior Location People Safety Structure Safety
Air Terminals

Yes

No

Yes

No

No

Yes

Down Conductors

Yes

No

Yes

Yes

No

Yes

Bonding

Yes

Yes

Yes

Yes

Yes

Yes

Grounding

Yes

Yes

Yes

Yes

Yes

Yes

Shielding

Yes

Yes

Yes

Yes

Yes

Yes

Surge Protection

Yes

Yes

Yes

Yes

Yes

Yes

Detection

Yes

Yes

Yes

Yes

Yes

Yes

Policies & Procedures

Yes

Yes

N/A

N/A

Yes

Yes

 

3. Practical Guidelines for Telecommunications Sites

A generalized, practical use of the above matrix, where relevant for telecom sites, is presented in this section.

3.1 Air Terminals

Lightning usually terminates on grounded objects sticking up in the air. Franklin rods are air terminals. Old Ben's designs, developed in 1752, divert lightning from rods in the air via conductors to rods in the ground, protecting important assets. This part of a lightning protection system (LPS) is based upon the principles of Path of Least Impedance. Nowadays, some vendors are promoting unconventional air terminal designs (Charge Transfer Array/Early Streamer Emitter, etc.), seeking to gain advantage over competitors. Caveat emptor. Of course, should lightning strike across the street from a telecom center and couple into its sensitive electronics via underground wiring, water pipes, buried conduits, and so on, then no type of air terminal sub-system has performed and it has no value. On telecom towers, ordinary sacrificial rods can protect sensitive antennae. In the main, the tower is the air terminal.

3.2 Bonding

Without proper bonding, all other elements of the lightning protection system are useless. Bonding of all metallic conductors in a telecom facility assures everything is at equal potential. When lightning strikes, all electrical equipment voltages will rise and fall at the same potentials. This protects against unequal voltages in separate sensitive signal and data systems. Bonding should connect all conductors to the same "Mother Earth." A partial listing includes antenna towers, shields on incoming coaxial cables, cable trays, cabinets and racks, computer room signal reference grids, telephone room equipment, conduits carrying various AC power and low-voltage DC current conductors, and AC power bus bars. Not convinced bonding is important? Check out NEC 250.90 through 250.104 for more details.

A recent inspection revealed a bare copper ground wire in contact with an interior electrical conduit. The result: A visible arcing mark caused by lightning's "flashover" with resulting destruction of nearby low voltage equipment. The solution: Either bond the two adjacent grounds together, or (better) use only insulated, not bare, wire for interior bonding.

3.3 Grounding

Low-resistance grounding provides an efficient destination for the "lightning beast." If site soils are composed of sand or rock, they are resistive, not conductive. If surrounding soils are clays or dirt with moisture present, they likely are conductive. "Good Grounds" are achieved by volumetric efficiencies. We recommend buried bare 4/0 copper wire – the so-called ring electrode or ring ground. Cadwelding® all-ground references adjacent to buildings should include security fences, tower legs, and all other adjacent metallic objects. The National Electrical Code Section 250 describes the perimeter ring concept as well as other grounding designs, such as rods, plates, water pipes (beware plastic pipes underground), metal frame of buildings, and concrete-encased electrodes. Choose your grounding design based upon localized conditions and the amount of available real estate at your location. Good grounding largely is a function of volumetric efficiencies. NEC 250.56 suggests a target earth resistivity number of 25 ohms for one ground rod. Lower is better. Yet sometimes 50+ ohms will be OK.

Another recent inspection, using an AEMC 3730 Ground Resistance Tester, showed grounding measurements of 450 ohms at a power pole ground wire drop. The result: Lightning bypassed this high-resistance ground and instead went into the telecom building via the overhead phase lines. The solution: Re-work power pole grounds to achieve lower ohms target resistance.

3.4 Surge Suppression

Surge suppression devices (SPDs aka TVSS) all function either by absorbing the transient as heat or crowbaring the transient to ground (or some combination thereof). They should be installed at main panel entries, at critical branch or secondary panels, and at plug-in outlets where low-voltage transformers convert AC power to DC current and voltage. SPDs also should be installed at signal and data line building entry points for critical electronic equipment. Included here are Cat. 5/6, coaxial lines, and twin lead and other copper wire circuits. Telephone punch blocks should be SPD-protected. Beware of the junk SPDs that proliferate in the marketplace. Beware of counterfeit or false UL and IEEE labeling. Beware of the "it sounds too good to be true" marketing hype employed by some vendors. Consider panel SPDs that have capabilities to remotely signal their operational performance. SPDs rank right behind bonding in the hierarchy of important steps to mitigate the lightning hazard.

Surge suppression is a complex subject, with many questions. Where and how to install SPDs? What SPD internal technologies are important? Which SPD codes and standards are important and which are vendor-influenced? How do UPS-protected circuits play into surge protection? What about fibre optic conductor vulnerabilities? For these and other considerations, find an authority not employed by SPD vendors for impartial and verifiable guidance. Feeling lucky and want to play the odds that lightning or power company surges never will enter your telecom facility? Just wait and Mother Nature will do the testing for you!

3.5 Codes and Standards

There aren't any lightning protection guidelines specific for the telecom industry. It is important that the wireless community consider adopting a contemporary lightning protection recipe. Taking a few items from NFPA 99 and NFPA 780, also adding in Motorola R56, stirring in some ingredients from IEEE 142 and IEEE 1100, mixing well with FAA-STD-019d and NASA-KSC-E0012E, and sprinkling on top some NEC 250 & 517 information would result is a very good final product for a pragmatic lightning protection standard. Some leadership is needed here. Please step forward…

4. Conclusion

Lightning is arbitrary, capricious, and stochastic – with odds of a strike approaching 1:1,000,000. A detailed and professional risk assessment exercise may produce meaningless guidance. Most people, when confronted with a conundrum of very low risk vs. very high consequences will chose to take no action towards lightning protection (perhaps because it's the path of least resistance). With emergency radio networks, the equation is different. When the communications net goes off-line, for whatever reason, the result is that ambulance, fire, and police resources and responses are compromised. This is an untenable situation that demands lightning protection for telecommunications facilities.